South Central/Southwest Wisconsin and North Central Illinois
Zone 3
Transmission system characteristics in Zone 3
ATC delivers power in Zone 3 with various transmission facilities including:
- Columbia-North Madison 345-kV lines,
- Columbia-Rockdale 345-kV line,
- Paddock-Rockdale 345-kV line,
- Paddock-Wempletown 345-kV line,
- Rockdale-Wempletown 345-kV line, and
- 138-kV facilities from the Nelson Dewey Power Plant, around the Madison area, and in the northwest and southeast portions of Zone 3.
Transmission system performance issues in Zone 3 include voltage instability, limited import capability, overloaded lines and equipment and low system voltages. The causes of these emerging issues include steady growth in certain areas, new power plants and different
generation dispatch scenarios.
Transmission system limitations in Zone 3
In our analysis of Zone 3, we identified low voltages, high voltages and transmission-facility overloads. Low voltages are located in the Verona, Beloit, Hustisford and Waunakee areas. Several overloads on 138‑kV and 69‑kV facilities in Zone 3 are emerging concerns.
Electric System Overview
Increases expected in population, employment – Population in Zone 3 is projected to grow about 0.9 percent annually between now and 2021, and employment is projected to grow about 1.3 percent each year for the same time period. Dane County is projected to realize the largest increase in population, and Sauk County is projected to have the largest increase in employment.
Electricity usage growing – Electric load is expected to grow approximately 1.38 percent annually through 2021 for all of Zone 3.
Transmission Projects in Zone 3
We have implemented two network projects in Zone 3 since the 2011 Assessment, most notably the Brodhead to South Monroe 69‑kV line rebuild project.
Our current plans in Zone 3 include 49 system reliability and economic projects between 2012 and 2026, 15 of which are driven by our new Study-Based Rating Methodology. These projects are in various stages of development. The most notable planned, proposed, provisional and asset renewal projects in Zone 3, along with their projected year of completion and the factors driving the need for the projects, are listed below.
Zone 3 includes the counties of:
- Columbia , WI
- Crawford (S) , WI
- Dane , WI
- Dodge , WI
- Grant , WI
- Green , WI
- Iowa , WI
- Jefferson , WI
- Lafayette , WI
- Richland , WI
- Rock , WI
- Sauk , WI
- Walsworth , WI
- Winnebago (N) , IL
Zone 3 Planned Projects
Project Description | In-service year | Need driver |
---|---|---|
Rockdale-Cardinal 345‑kV line | 2013 | Overloads and low voltages, improve transfer capability to Madison area, avert voltage collapse, lower system losses |
Zone 3 Proposed Projects
Project Description | In-service year | Need driver |
---|---|---|
Sun Valley Tap-Oregon 69‑kV line rebuild | 2016 | Overloads and improve line condition and area voltages |
Badger Coulee: La Crosse area-North Madison-Cardinal | 2018 | Reliability, economics and public policy |
Spring Valley-North Lake Geneva 138‑kV line construction | 2019 | Overloads and low voltages, provide network service |
Cardinal Bluffs: Dubuque County area-Cardinal 345-kV line construction | 2019 | Reliability, economics and public policy |
Zone 3 Provisional Projects
Project Description | In-service year | Need driver |
---|---|---|
Colley Road-Brick Church 69‑kV line rebuild | 2018 | Overloads and low voltages |
Gran Grae-Boscobel 69‑kV line rebuild | 2019 | Overloads |
Lake Delton-Birchwood 138‑kV line construction | 2020 | Overloads and low voltages |
Cardinal-Blount 138‑kV line construction | 2020 | Overloads and low voltages |
Hubbard-East Beaver Dam 138‑kV line construction | 2022 | Overloads and low voltages |
West Middleton-Pheasant Branch 69‑kV line rebuild | 2022 | Overloads and low voltages |
Zone 3 Asset Renewal Projects
Project Description | In-service year | Need driver |
---|---|---|
Doylestown-Rio Pumping Station 69‑kV line rebuild | 2013 | Condition and performance |
Dam Heights-Portage 69‑kV line rebuild | 2016 | Condition and performance |
Darlington-Hillman 138‑kV line rebuild | 2016 | Condition and performance |
Concord-Rubicon-Butler Ridge-Hartford 138‑kV line rebuild | 2016 | Condition and performance |
Belmont-Rewey 69‑kV line rebuild | 2018 | Condition and performance |
Boscobel-Lone Rock 69‑kV line rebuild | 2018 | Condition and performance |
West Middleton-Stagecoach 69‑kV underground cable replacement | 2019 | Condition and performance |